Serviceline Industrial Sensors
Serviceline Explosion Protection

Ej tillgänglig för köp

Ej tillgänglig för köp
Ej tillgänglig för köp

AS-Interface I/O module VBA-4E3A-G20-ZEL/M1L-P2

VBA-4E3A-G20-ZEL/M1L-P2
  • A/B node with extended addressing possibility for up to 62 nodes
  • Inputs for 3-wire sensors
  • Outputs for DC roller motors (drum motors)
  • Connection of motors and sensors via M8 connectors
  • Configurable start/stop ramps
  • Communication monitoring
  • Power supply of the inputs and outputs from the external auxiliary voltage
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Cable piercing method with gold plated contact pins

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Ladda ned datablad som PDF::


Utdrag ur datablad: Tekniska data för  VBA-4E3A-G20-ZEL/M1L-P2

Product Description
G20 motor control module for Interroll EC310, Interoll EC5000 24V AI, Rulmeca BL3, Itoh Denki PM500XK, Itoh Denki PM500XC
General specifications
Node typeA/B node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
UL File NumberE223772 "For use in NFPA 79 Applications only"
MTBF98 a
Compatible roller motorsInterroll EC310, Interroll EC5000 24V AI (20W / 35W / 50W), Rulmeca BL3, Itoh Denki PM500XK, Itoh Denki PM500XC
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor supply or speed signal overload or external auxiliary voltage UAUX missing
LED ERRMotor fault: 2 LED yellow
LED PWRAS-Interface voltage; green LED
green: voltage OK
green flashing: address 0 or sensor supply overload or speed signal overload or external auxiliary voltage UAUX missing
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 2 LED yellow
LED FUSEMotor power supply; 2 green LEDs
LED DIRMotor rotation direction; yellow LED
LED MOTMotor active; 2 yellow LEDs
Electrical specifications
Auxiliary voltage (output)18 ... 30 VDC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 35 mA
Input
Number/Type2 Inputs for 3-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Current loading capacity500 mA , overload and short-circuit protected
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2
0 (undamped) ≤ 0.5 mA
1 (damped) ≥ 2.0 mA
Signal delay< 1 ms (input/AS-Interface)
Input filter2 ms
Output
Number/Type2 outputs for DC roller motors (MOT1, MOT2)
Supplyfrom external auxiliary voltage UAUX
Current3.5 A continuous current , 5 A (<2 s) , max. 7.5 A (<0,3 s) per motor
Overload protectionfuse , I2t = 53.7 A2s
Velocity signal1.4 … 13 V at no-load
Ri = 5.6 kΩ, RLOAD ≥ 35 kΩ
Control via parameter P2:0
Rotation direction signalOff / ≥ (UAUX - 1.0 V) at no-load
Ri = 5.6 kΩ, RLOAD ≥ 5 kΩ
AS-Interface data bit D2 = 0: UD = Off
Motor faultDigital input NPN, U0 = 3.3 V, Ri = 52 kΩ
0 (no error) ≥ 40 µA
1 (error) ≤ 30 µA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.A.E
IO code7
ID codeA
ID1 code6
ID2 codeE
Data bits (function via AS-Interface)InputOutput
D0 MOT1 fault MOT1 operation
D1 MOT2 fault MOT2 operation
D2 IN1 MOT1/MOT2 rotation direction
D3 IN2 -
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP54 according to EN 60529
ConnectionAS-Interface, AUX: Insulation piercing technology
Yellow flat cable/black flat cable
Inputs/outputs: M8 round plug connector in accordance with EN 61076-2-104
Inputs: LF004-GS1-A (4-pin, bushing contacts, screw lock, A-coded)
Matching connector: LM004-Gx1-A or similar
Outputs: NF005-SS1-B (5-pin, bushing contacts, snap lock, B-coded).
Matching connector: NM005-Sx1-B or similar
Mass220 g
Dimensions
Height27.5 mm
Width131.5 mm
Length54 mm
Mounting2 clips with ∅ 8 mm drill hole
Cable length1 m
NoteThe flat cable routing is designed for 100 actuation cycles

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-4E3A-G20-ZEL/M1L-P2

Informative Literature: VBA-4E3A-G20-ZEL/M1L-P2

Language Selection:
LiteratureLanguageFile TypeFile Size
Portfolio overview G20 modules / Portfolio-Übersicht G20-ModuleALLPDF121 KB

Product Documentation: VBA-4E3A-G20-ZEL/M1L-P2

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Instruction leaflet / BeipackzettelALLPDF225 KB
Manuals
Manual VBA-4E3A-G20-ZEL/M1L-P2 and VBA-4E3A-G20-ZEL/M1L-P6ENGPDF1907 KB

Design / Simulation: VBA-4E3A-G20-ZEL/M1L-P2

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP1692 KB

Approvals: VBA-4E3A-G20-ZEL/M1L-P2

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
US CA UL AS-InterfaceCoC UL-US-L223772-13-82803102-1ALLPDF175 KB

Software: VBA-4E3A-G20-ZEL/M1L-P2

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
Add-On Instructions for RSLogix/Studio 5000 / Add-On-Befehle für RSLogix/Studio 50004/2020ZIP23385 KB

Associated Products: VBA-4E3A-G20-ZEL/M1L-P2

Accessories

AS-Interface Handheld with accessoryfa